Dwyer TSWB Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Router Dwyer TSWB herunter. Dwyer TSWB User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
The Series TSWB Digital Temperature Switch has a high and a low set
point for controlling the water temperature. The low set point can either be
manually or automatically reset. This control also has a conductivity probe
input. This input supplies12 VAC to the probe to check for low water con-
dition. There are three relay outputs which can be assigned in the field to
the high temperature set point, low temperature set point or the low water
level input. The Model TS2-K configuration key can make configuring mul-
tiple controls quick and easy.
Model References
Installation
NOTE: Unit must be mounted away from vibration, impacts, water and
corrosive gases.
··
Cut hole in panel 2.80 x 1.14 inches).
··
Apply silicone (or rubber gasket) around the perimeter of the hole to pre-
vent leakage.
··
Insert unit into hole of panel.
··
Slide removable fitting clips onto unit from the back until secure to panel.
··
Wiring diagram is displayed on the top of the unit.
Note: DO NOT INSTALL PROBE CABLE NEAR POWER CABLES.
Display Color
0 = Red
1 = Green
TSWB Digital Temperature/Water Level Switch
Specifications - Installation and Operating Instructions
Bulletin T-20-TSWB
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
SPECIFICATIONS
Probe Range: PTC -58 to 302ºF (-50ºC to 150ºC); NTC -58 to 230ºF
(-50ºC to 110ºC).
Probe Temperature Input: (Selectable by parameter) PTC1000 probes
(25ºC-1000 Ohm) / NTC.
Probe Level Input: Conductivity Probe: max Voltage 12 VAC. Sensitivity
established from factory at 100KOhm.
Output: R1 SPST NO Relay Resistive load 5A @ 250 VAC.
R2 SPST NC Relay Resistive load 5A @ 250 VAC.
R3 SPDT Relay Resistive load 16A @ 240 VAC.
Horsepower Rating: 1HP -- 10FLA, 60LRA 250 VAC.
Control Type: On/Off.
Power Requirement: 115 VAC ± 10%, 230 VAC ± 10%, 24 VAC/DC ±
10%, 12 VAC/DC ± 10%.
Power Consumption: 4VA (230V/115V) 1.5VA (24V/12V).
Accuracy: Better than 1% of full scale.
Display: 3-digit, red 1/2˝ digits.
Resolution: 1º (3 digits).
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 32 to 158ºF (-30 to 70ºC).
Storage Temperature: -4 to 176ºF (-30 to 80ºC).
Weight: 3.5 oz.
Front Protection: IP64.
Agency Approvals: CE, UL, cUL.
LOVE CONTROLS DIVISION
Wiring Diagram
TSWB -
Power Supply
1 = 115 VAC
2 = 230 VAC
3 = 12 VAC/VDC
4 = 24 VAC/VDC
Units
0 = °F
1 = °C
2-63/64
[75.69]
7/32
[5.33]
2-29/64
[62.23]
1-21/64
[33.73]
1-7/64
[28.19]
2-49/64
[70/36]
T-20-TSWB 3/10/08 10:48 AM Page 1
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - DWYER INSTRUMENTS, INC

The Series TSWB Digital Temperature Switch has a high and a low setpoint for controlling the water temperature. The low set point can either bemanuall

Seite 2

Parameter ProgrammingProgramming the High and Low Set Point (HSP and LSP).• Press SET HSP text will appear on the display.• Press SET again. The value

Kommentare zu diesen Handbüchern

Keine Kommentare