The Series TSF Thermocouple FM Approved Limit Control provides
audible alarm status along with a robust 16 amp relay output. Unit allows
the user to easily select automatic or manual reset along with 13 other
parameters. The TSF series has a built in reset button on the front panel
or can accept an external reset.
The ease of programming and low price make the TSF series the best
value limit control on the market.
INSTALLATION
Note: Unit must be mounted away from vibration, impacts, water and
corrosive gases.
Cut hole in panel 2.80 x 1.14 inches (71 X 29 mm).
Use the included gasket, or apply silicone around the perimeter of the
hole to prevent leakage.
Insert unit into the hole in panel, and secure using the included
mounting clips.
Wire the unit per the wiring diagram on the product label or in IOM.
Series TSF Thermocouple Limit Control
Specifications - Installation and Operating Instructions
Bulletin E-90-TSF
LOVE CONTROLS DIVISION
Phone: 219/879-8000 www.love-controls.com
DWYER INSTRUMENTS INC.
Fax: 219/872-9057 e-mail:[email protected]
P.O. BOX 338 - MICHIGAN CITY, INDIANA 46360, U.S.A.
2.95
[75]
1
.34
[
34]
2
.72
[
69]
1
.10
[
28]
PROBE*
INPUT
+
-
POWER
SUPPY
OUTPUT
NC
COM NO
1
TS2-K
234 56789
* Use ungrounded thermocouples only with 12 VAC/VDC and 24
VAC/VDC models.
SPECIFICATIONS
Probe Range: 32 to 999°F (0 to 700°C) for Type J thermocouple; 32
to 999°F (0 to 999°C) for Type K or S thermocouples.
Input: Type J, K, or S thermocouple.
Output: SPDT relay rated 16A @ 240 VAC resistive.
Horsepower Rating (HP): 1 HP.
Control Type: ON/OFF; manual/automatic reset.
Power Requirements: 115 VAC, 230 VAC, 12 VAC/VDC or 24
VAC/VDC (depending on model).
Power Consumption: 4 VA.
Accuracy: ±1% FS.
Display: 3-digit, red, 1/2˝ (12.7 mm) digits and sign.
Resolution: 1°.
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 32 to 150°F (0 to 65°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: IP64.
Agency Approvals: CE, FM, UL.
Wiring Diagram
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - 234 56789

The Series TSF Thermocouple FM Approved Limit Control providesaudible alarm status along with a robust 16 amp relay output. Unit allowsthe user to eas

Seite 2

SPr0r1r2r3d0c0c2c3P1P5P6H1H5DescriptionSet PointDifferential or HysteresisLower Limit for SPHigher Limit for SPControl ResetHigh or low limit controlM