Introduction
The Series DCT500ADC Timer Controller is a timing system for pulse-jet type dust
collectors or pneumatic conveying systems in either continuous or on-demand clean-
ing applications. It is provided with either 4, 6, or 10 channels. The DCT500ADC was
designed for ease of installation in your dust collector system. For installations requir-
ing fewer channels than available on the board, a shorting plug is provided to allow
selection of the last used channel. Time-on and time-off settings are selected using
two potentiometers. High-limit and low-limit control inputs are provided for use with
on-demand systems. When used in a continuous mode the high-limit input is
jumpered.
Installation
Warning: Always replace the fuse with the proper type and rating.
The fuse is Type 3 AG fast acting 3 Amp @ 250V. DO NOT use slow-
blow type fuses. Failure to comply with this requirement will void man-
ufacturer’s warranty.
This equipment is intended to be powered using a recognized Class 2
power supply. If powered from a DC bus a suitable transient protection
device meeting Installation Category II requirements must be used.
Protection provided by the equipment may be impaired if the equipment
is used with accessories not provided or recommended by the manu-
facturer, or is used in a manner not specified by the manufacturer.
Power Requirements
The DCT500ADC Series controller is designed for operation with a DC power supply.
The supply voltage must be between 10 VDC and 35 VDC. Exceeding 35 VDC may
damage the unit. The solenoid outputs are driven from the power supply so the sole-
noids must be rated for operation at the power supply voltage. The solenoids are
connected as shown in the wiring diagram and must not be connected to any other
external circuit. The solenoid common is the positive (+) lead and is internally con-
nected to the fused positive (+) supply. The individual outputs are switched to the
negative (-) supply input through an open drain field effect transistor (FET). The out-
puts are protected for inductive flyback transients of the solenoids.
Location
The system must be located in an enclosure that meets relevant safety standards and
electrical codes. There are no other special orientation requirements. Mount it using
the four mounting holes in the baseplate. The baseplate back is flush, so no special
spacers are needed to accommodate obstructions except for those imposed by the
location itself.
SPECIFICATIONS
Output Channels: 4, 6, & 10 channels.
Voltage Requirements: 10 to 35 VDC ( ).
Power Consumption: 0.6 W.
Input Power: 106 W @ 35 VDC ( ) max.
Load: 3A max per channel.
Fuse: Type 3 AG, 3A @ 250 VAC (~).
Ambient Operation Temperature: -40 to 149°F (-40 to 65°C).
Storage Temperature Limits: -40 to 176°F (-40 to 80°C).
Humidity Conditions: 5 to 95% noncondensing.
On Time: 50 to 500 msec.
On Time Accuracy: ±5% of setting.
On Time Repeatability: ±1 msec.
Off Time: 1 to 180 seconds.
Off Time Accuracy: 5% of setting.
Pollution Degree: 2.
Altitude: 6560 ft (2000 m) max.
Environment: Indoor use, must be installed in a weather-proof enclosure for out-
side applications.
Weight: 9 oz (255 g).
Agency Approvals: CE.
Connections
The power and solenoid connections are located at the lower edge of the board. The
terminal block is a “Euro” style connector system that clamps the wire within the con-
nector body. The connector will accept wire sizes from 14 to 22 gages. These termi-
nals should be torqued to 5 in. lb. The connectors are specified for single connection
but multiple wires may be connected to a single lug provided local codes allow this
and good workmanship practices are followed. When using stranded wire, make sure
that there are no “stray” strands. These may cause system failure or damage.
Connect the (+) (-) power to (+) and (-). Connect the solenoids between the selected
output and the solenoid common. Solenoid common and (+) are internally connect-
ed through fuse. Refer to Figure 2-1.
The wire should be stripped to no more than 0.25 in. A strip gauge is provided at the
lower right corner of the board. Longer than this may cause shorts. Switches con-
nected to the control inputs at the top of the board must be isolated normally open
contacts connected only to the relevant terminal and to the common terminals.
The following subparagraphs describe the external switch connections. Refer to fig-
ure 2-1 for switch connection illustration.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361,U.S.A. Fax: 219/872-9057 e-mail: [email protected]
Specifications – Installation & Operating Instructions
Series DCT500ADC Timer Controller
BULLETIN E-98ADC
1/16
[1.59]
1/2
[12.70]
1-3/16
[30.16]
6-1/4
[158.75]
6-3/4
[171.45]
4-1/4
[107.95]
4-7/8
[123.83]
TIME OFF
TIME ON
SEC
mSEC
F1
E-98ADC:Bulletin E-98 DC5.0 7/8/09 8:44 AM Page 1
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - DWYER INSTRUMENTS, INC

IntroductionThe Series DCT500ADC Timer Controller is a timing system for pulse-jet type dustcollectors or pneumatic conveying systems in either contin

Seite 2

FIGURE 2-1 Switch ConnectionsExternal Limit Switch ConnectionThe controller may be used with an external pressure limit switch or sensor to pro-vide d

Kommentare zu diesen Handbüchern

Keine Kommentare