Series DPMA-5 Adjustable LCD Digital Panel Meters
Specifications - Installation and Operating Instructions
Bulletin G-64
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Series DPMA-5 Adjustable Panel Meter offers a large 1˝, 3-1/2 digit
display for easy viewing in a standard 1/8 DIN package. Unit accepts
voltage inputs with a wide bipolar span and zero adjustment. Standard
features include field selectable engineering units and decimal point
positions. Choose from red, amber, or green segments for easy viewing
at a distance. A separate 24 VDC power supply is required for the
operation of the backlight.
INSTALLATION
The Series DPMA-5 is designed to snap into a 3.62˝ (92 mm) W x 1.77˝
(45 mm) H panel cutout. No additional hardware is required.
WIRING
Three sets of jumper pins are located on the back of the meter. Move
the jumper to fit over the appropriate pins which correspond to the
desired signal input voltage, supply voltage and decimal point position.
An external 12 or 24 VDC power supply is required to power the meter
and should be connected to the screw terminal marked with “+pwr-” (see
Figure 2). The backlighting requires a separate 24 VDC power supply
and should be connected to terminals identified with “+B/L-”.
SPECIFICATIONS
Input: 0 to 200 mVDC, 0 to 5 VDC, or 0 to 10 VDC.
Input Impedence: 390KΩ nominal.
Accuracy: ±(0.05% FS + 1 count).
Power Supply: 12 VDC or 24 VDC.
Backlight Power Supply: 24 VDC @ 35 mA typical.
Span and Zero: Adjustable. (±1999 counts).
Display: 3-1/2 digits, 7 segments, 1˝ (25.4 mm) H.
Decimal Points: 3-position, user selectable.
Engineering Units: DPMA-XXX: °F, °C, %, PSI; DPMA-XXXP: V, A,
KW, PF.
Polarity: Automatic, “-” displayed.
Operating Temperature: 32 to 122°F (0 to 50°C).
Storage Temperature: -4 to 158°F (-20 to 70°C).
Mounting: Snap-in panel mount or clamp (gasket included).
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-up: 10 minutes typical.
Weight: 4 oz (113.4 g).
Agency Approvals: RoHS.
V
A
KW
PF
°F
°C
P
SI
%
P Models
15/32
[
12]
1
-1/8
[28.5]
3
-25/32
[96]
1-59/64
[49]
5
/64
[1.9]
63/64
[
25]
1
3/64
[5]
1-57/64
[
48]
1-49/64
[45]
M
OUNTING BRACKET
OUTLINE REAR VIEW
PANEL CUTOUT
FOR SNAP IN MOUNTING
3-5/8
[
92]
4
-29/64
[
113]
(R.010 MAX) 4 PLCS [.25 mm]
3-15/32
[
88] REAR HOUSING
1
-59/64
[49]
Figure 1
Figure 2
The unit accepts 200 mVDC, 5 VDC, or 10 VDC. Wire the input signal to
terminal “+sig-” and put a jumper between “-sig” and “-pwr” (see Figure
3).
Figure 3
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - DWYER INSTRUMENTS, INC

Series DPMA-5 Adjustable LCD Digital Panel MetersSpecifications - Installation and Operating InstructionsBulletin G-64DWYER INSTRUMENTS, INC. Phone: 2

Seite 2

OPERATIONSelecting Engineering UnitsFour sets of jumper pins are located in the back of the meter, between themeter and the adder board. Move th

Kommentare zu diesen Handbüchern

Keine Kommentare