1. Push tab on bottom of cover and lift cover from back plate (See Figure 1).
2. Select the mounting location, away from diffusers, lights or any external
influences.
3
. Mount transmitter on a vertical surface to a standard electrical box using the two
#
6 M2C type screws provided.
4
. Pull wires through sub base hole and make necessary connections.
5. Reattach cover to base plate.
(#
Use maximum 18 AWG wire for wiring to terminals. Refer to Figure 5 for wiring
i
nformation.
$/5/-=38780>;;/7=+7.'85=+1/ >=9>=<
Prior to wiring, verify that the current/voltage selection jumpers (PJ1, PJ2, and PJ5)
are set to the desired output type. Refer to Figure 2 to locate the selection jumpers.
See Figure 3 for diagram of the current/voltage selection jumper. For voltage output
selection, the output can be 0 to 10 VDC, 0 to 5 VDC, 2 to 10 VDC or 1 to 5 VDC.
See Figure 4 for the type of voltage output selection jumper (PJ5).
>;;/7='85=+1/ >=9>=<
O
n the CDT, the transmitter may be wired for current or voltage output for both carbon
d
ioxide and temperature. On the CDTR, the transmitter may be wired for current or
v
oltage output for both carbon dioxide and humidity. The transmitter can be powered
with either 16 to 35 VDC or 19 to 28 VAC. Wire the transmitter according to Figure 5.
#
/68=/3<95+B
F
or models that are ordered without an integral LCD display, remote display Model
A-449 can be used to display the temperature, humidity, and carbon dioxide. The mini
USB plug of the remote display plugs into the receptor on the side of the housing.
After a short warm up time, the display will begin to show the current temperature and
carbon dioxide measurements unless configured by the user to show humidity and
carbon dioxide, only temperature, only humidity, or only carbon dioxide.
%&!#%#$
Before any adjustment can be made to the transmitter, the Menu Lockout Jumper
(PJ4) must be set to the ˝On˝ position (See Figure 6).
$$E&!#%#$
Step 1: To enter the menu structure, press and simultaneously for
5 seconds (display will show RON parameter).
Step 2: Press or to cycle between menu items.
Step 3: Press to edit the value for the displayed menu item (SET will appear
on display).
Step 4: Press or to adjust the value of the menu item.
Step 5: Press to save the changes (SET will disappear).
Step 6: Repeat Steps 2 through 5 for each of the parameters.
Step 7: To exit the menu at any time, press and hold and
simultaneously for 5 seconds or wait 10 seconds without pushing any buttons.
HINGE
BOTTOM TAB
SELF-LATCHING
COVER
MOUNTING
BACK PLATE
MOUNTING
SCREWS
T
O REMOVE COVER
A
PPLY PRESSURE TO
B
OTTOM TAB WHERE
I
NDICATED AND THE
T
WO PARTS WILL
B
ECOME UNHINGED
A
T TOP
R
EVERSE PROCESS
T
O APPLY COVER
CURRENT
OUTPUT
VOLTAGE
OUTPUT
C
C
VV
F
2 to10 V
4 to 20 mA
0 to 10 V
0 to 20 mA
0 to 5 V
0 to 10 mA
1 to 5 V
2 to 10 mA
P
ASSIVE
TEMPERATURE
S
ENSOR
RELAY
CONTACT
P
OWER
SUPPLY
T
EMP OR RH
RECEIVER
CO2
RECEIVER
31>;/#/68?+5 08?/;;86+-4!5+=/
&#>;;/7='85=+1/ >=9>=
$/5/-=387>69/;!7.!
31>;/ >=9>=#+71/$/5/-=387>69/;!
31>;/-=3?/ >=9>=(3;3713+1;+6
31>;/3+1;+6E 0E3;->3=8+;.
ENABLED
DISABLED
OFF
MENU MENU
PJ4
PJ4
OFFON
ON
31>;//7>8-48>=>69/;
Optional relay can be used as either a dry contact or low voltage
switched circuit up to 2 A at 30 VDC.
%