Dwyer BCV Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Zubehör fürs Wasser Dwyer BCV herunter. Dwyer BCV User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 1
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Dwyer Instruments Inc.
P.O. Box 373, 102 Indiana Hwy. 212
Michigan City, IN 46361 USA
Tel. 219/879-8000 - Fax 219/872-9057
E-mail: [email protected] - Website: www.dwyer-inst.com
Check Valve - Ball Series
Characteristics
Working pressure at 20°C (73°F) water temperature:
- D20 - D63 (½”-2”): PN 16 bar (240 p.s.i.)
- D75 - D110 (2½”-4”): PN 10 (150 p.s.i.)
Description
1. Body PVC / CPVC
3. Ball PVC / CPVC
4. Union nut PVC / CPVC
5. End connector PVC / CPVC
6. Closing ring PVC / CPVC
7. Body o-ring EPDM / Viton®
8. End connector o-ring EPDM / Viton®
9. Seal-carrier PVC / CPVC
10. Screen PP
Material
Components
Assembly Instructions
Solvent socket or threaded unions
Loosen the union nuts (4) and separate these and the end connectors (5) from the valve body. Pass
the pipe through the nuts and then place the bushes over the ends of the pipe. The solvent unions
should be glued onto the pipe using a PVC adhesive and pressure should not be applied to the
system until a drying period of at least 1 hour per 14.5 psi of working pressure has elapsed. In the
case of threaded unions, PTFE tape should be applied to the male threads. The pipes can now be
attached to the valve by hand tightening down the nuts.
Installation may be vertically and horizontally
WARNING: Minnimum return pressure: 0,2 bar (3 psi)
Foot valve
Use the screen instead of the end connector of the fluid entrance to transform the check valve into a
foot valve.
Foot valves are a particular type of check valves which are installed on the base of an aspiration pipe
of a pump to prevent the impulsion pipe from emptying.
The valve must be installed between the pump and the tank in order to let the fluid access the pump
and stopping it when returning to the tank. The entry of the valve is protected by a screen filter to
prevent the entry of unwanted elements which could exist in the tank or deposit.
• WE RESERVE THE RIGHT TO CHANGE ALL OR PART OF THE FEATURES OF THE ARTICLES OR CONTENTS OF THIS DOCUMENT, WITHOUT PRIOR NOTICE.
ENGLISH
EDITION: 12 - 2006
R
20 years / water flow
Temperature
Pressure
18
16
14
12
10
8
6
4
2
0
0 10 20 30 40 50 60 70 80 90
°C
32 50 68 86 104 122 140 158 176 194
°F
bar
psi
PVC
CPVC
270
240
210
180
150
120
90
60
30
0
PN 10
PN 16
D20- ½” D25 - ¾” D32 - 1” D40 - 1¼” D50 - 1
A B A B A B A B A B A B A B A B
1.65 0.13 1.47 0.05 4.36 0.08 4.87 0.15 6.41 0.002 12.53 0.05 12.32 0.05 7.13 0.009
2.33 0.24 2.01 0.054 4.89 0.11 6.21 0.17 11.3 0.02 14.9 0.07 14.95 0.06 15.91 0.04
3.34 0.44 2.34 0.09 5.44 0.15 7.52 0.21 18.76 0.16 17.12 0.11 19.53 0.11 28.58 0.13
3.85 0.52 2.95 0.18 5.89 0.21 10.61 0.27 25.05 0.34 21.7 0.16 25 0.17 37.22 0.22
4.52 0.69 3.6 0.29 7.01 0.26 12.53 0.34 28.44 0.41 27.36 0.28 32.6 0.28 45.61 0.53
- - 4.03 0.36 9.23 0.39 15.23 0.4 - - 32.02 0.37 41.43 0.55 58.5 0.64
- - 4.21 0.38 - - - - - - 37.68 0.43 - - - -
½” D63 - 2” D75 - 2½” D90 - 3”
Cv Kv
D20 - ½” 7 99
D25 - ¾” 9 128
D32 - 1” 22 308
D40 - 1¼” 32 453
D50 - 1½” 56 795
D63 - 2” 73 1040
D75 - 2½” 135 1932
D90 - 3” 193 2754
Pressure loss diagram
Check valve
Foot valve
Pressure / temperature diagramm
Relative flow chart
A= Flow (m³/h)
B= Pressure loss (bar)
Pressure loss diagram
FLOW
DIRECTION
Kv= l/min at 1 bar
Cv= GPM at 1 psi
Pressure loss
Flow
100
1.000
10.000
1
mca
(l/min)
10
26,4
264
2.642
(GPM)
15
psi
150
0
D2
½
0
-
25
D
-
¾
D32
1”-
-
D
40
D
½
50 -
1
D6
3 -
2
5
D7
-2 ½”
D 0
-
3
9
0
Bcv-1
Seitenansicht 0
1

Inhaltsverzeichnis

Seite 1 - Foot valve

Dwyer Instruments Inc.P.O. Box 373, 102 Indiana Hwy. 212Michigan City, IN 46361 USATel. 219/879-8000 - Fax 219/872-9057E-mail: [email protected] - W

Kommentare zu diesen Handbüchern

Keine Kommentare