Series 2800 Current to Pressure Transducer
Specifications - Installation and Operating Instructions
Bulletin V-4
The Series 2800 Current to Pressure Transducer converts a current
input to a linearly proportional pneumatic output pressure. This unit
utilizes a closed loop pressure feedback system that closely controls
output and compensates for vibration, mounting angle, temperature, and
supply pressure variations. These characteristics make this unit ideal for
field mounting on a valve. The control mechanism is a piezoceramic
actuator encapsulated in a protective skin, which provides a constant
defense against humidity and contaminants. These features make this
unit ideal for use in demanding applications. The 2800 also comes in a
NEMA 4X enclosure and is field reversible. It is FM and CSA approved
intrinsically safe, as well. For ease of installation, this model has input
and output ports on both the front and back and can be easily panel
mounted.
SPECIFICATIONS
Service: Oil free, clean dry air filtered to 40 microns.
Input Signal: 4-20 mA.
Air Supply: Minimum: 5 psig (0.3 bar) above maximum output;
Maximum: 100 psig (6.9 bar).
Output: 3 to 15 psig (0.2 to 1.0 bar), 6 to 30 psig (0.4 to 2.1 bar).
Accuracy: ±0.1% of span.
Hysteresis: ±0.1% of span.
Repeatability: ±0.1% of span.
Deadband: 0.02% of span.
Power Requirement: Loop powered.
Temperature Limits: Operating: -40 to 160°F (-40 to 71°C); Storage: -
40 to 200°F (-40 to 93°C).
Pressure Connections: 1/4˝ female NPT.
Electrical Connection: 1/2˝ female NPT.
Air Consumption: 0.025 scfm (0.01 l/s) at midrange typical.
Output Capacity: 4.5 scfm (2.1 l/s) at 25 psig (1.7 bar) supply; 12.0
scfm (5.7 l/s) at 100 psig (6.9 bar) supply.
Enclosure: Chromate-treated aluminum with epoxy paint.
Enclosure Rating: NEMA 4X (IP65) and Intrinsically safe.
Weight: 0.8 lb (0.37 kg).
Agency Approvals: CSA, CE, FM.
Model
2813-WP
2816-WP
Input
4-20 mA
4-20 mA
1
[25.4]
Ø1/8
[
Ø3.17]
1-1/2
[38.1]
1-19/64
[33.0]
1-51/64
[45.7]
3-11/16
[
93.7]
MOUNTING HOLES
#10-32 UNF-2B X 3/8 DP
2 PLCS
2-3/16
[
55.4]
2
-15/16
[74.7]
22 GA. WIRE LEADS
APPROX. 18˝ LONG
POS, NEG, GRD
3-1/8
[
79.2]
3
3/64
[13.1]
25/64
[9.72]
4
9/64
[19.4]
1
/2 NPT
Ø1-1/8
[Ø28.7]
IN & OUT PORTS
1/4-18 NPT
4 PLCS
Output
3-15 psig (0.2-1.0 bar)
6-30 psig (0.4-2.1 bar)
PROXIMITY CONTROLS
Phone: 219/879-8000 www.dwyer-inst.com
A DIVISION OF DWYER INSTRUMENTS, INC.
Fax: 219/872-9057 e-mail: [email protected]
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A.
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - PROXIMITY CONTROLS

Series 2800 Current to Pressure TransducerSpecifications - Installation and Operating InstructionsBulletin V-4The Series 2800 Current to Pressure Tran

Seite 2 - BLACK LEAD (-)

INSTALLATIONThe Series 2800 transducer is a force balance device in which the piezoactuator is positioned in relation to a nozzle as the input signal

Seite 3

Reverse Acting CalibrationWhen calibrated to operate in the reverse acting mode the minimuminput signal produces the maximum output pressure

Seite 4

©Copyright 2013 Dwyer Instruments, Inc. Printed in U.S.A. 8/13