OPERATING INSTRUCTIONS
Series 681
SANITARY PRESSURE TRANSMITTERS
GENERAL INFORMATION
Your Dwyer Series 681Sanitary Pressure Transmitter has been carefully tested and
calibratedbefore shipment and it should be handled with the same care given any
precision instrument. Detailed performance information is listed on the specification
bulletin for the transmitter.
The 681 is designed according to 3A Standard #37-01 for sanitary installations. It has
a rugged MICRO-TIG welded stainless steel housing and is exceptionally insensitive to
vibration, shock, EMI/RFI interference and other environmental extremes. The 681 is
insensitive to the thermal shocks typical of CIP and SIP installations.
INSTALLATION NOTES
Series 681 should not require adjustment at installation. If adjustments are made it
is important to replace and tighten the zero and span screws (with O-rings) to
prevent moisture from entering.
The 681 is vented through the cable. Connections to the cable should be made in a
dry junction box vented to atmosphere. Insure that moisture cannot enter the end of the
cable.
The 681 is shipped with a rubber boot over the stainless steel pressure sensing
diaphragm to protect the diaphragm during shipment, storage, and handling prior to
installation. This boot should not be removed until the transmitter is to be installed and
should be used whenever the unit is removed from its installation. Do not contact the
diaphragm with sharp objects, screwdrivers or other mechanical devices.
Environment - The Series 681 Transmitter is designed to be used with any gas or liquid
compatible with 316L stainless steel (316 for ranges > 30 psig). It is designed to be
splash and drip proof for wash-down cleaning and can also be completely submerged
with the exception of the open end of the electrical cable.
Cleaning - The pressure sensing diaphragm will withstand normal high pressure
washing and partial vacuums created by fast cooling of steam sterilized tanks. However,
be sure not to exceed the proof pressure (listed on specification sheet). In high pressure
washing, care should be taken not to spray directly on diaphragm as it could result in
exceeding the proof pressure. The 681 can also be cleaned by dipping the diaphragm
in a container of cleaning solution or by wiping gently with a soft cloth.
Temperature Limits - The operating temperature limits of the 681, based on the limits
of the electronics, are -40
o
F to 260
o
F.
Thermal Effects 20
o
F to 180
o
F range
Zero Shift ± 2.00% F.S./100
o
F
Span Shift ± 2.00% F.S./100
Mounting - The 681 will mount directly to a mating tri-clover flange along with a tri-clover
type clamp and gasket. (2 inch tri-clover for ranges up to 30 psig and 1.5 inch for higher
ranges.)
Note: The output signal is not appreciably affected by clamping forces so it is not neces-
sary to orient the flange circle to any special position for best performance.
LIMITED WARRANTY AND LIMITATION OF LIABILITY
DWYER warrants its products to be free from defects in materials and workmanship, subject to
the following terms and conditions: Without charge, DWYER will repair or replace products
found to be defective in materials or workmanship within the warranty period; provided that:
a) the product has not been subjected to abuse, neglect, accident, incorrect wiring not our own,
improper installation or servicing, or use in violation of instructions furnished by DWYER;
b) the product has not been repaired or altered by anyone except DWYER or its authorized
service agencies;
c) the serial number or date code has not been removed, defaced, or otherwise changed; and
d) examination discloses, in the judgment of DWYER, the defect in materials or workmanship
developed under normal installation, use and service;
e) DWYER is notified in advance of and the product is returned to DWYER transportation
prepaid.
Unless otherwise specified in a manual or warranty card, or agreed to in a writing signed by a
DWYER officer, DWYER pressure and acceleration products shall be warranted for one year
from date of sale.
The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not
limited to, any implied warranty of merchantability for a particular purpose.
DWYER’s liability for breach of warranty is limited to repair or replacement, or if the goods
cannot be repaired or replaced, to a refund of the purchase price. DWYER’s liability for all other
breaches is limited to a refund of the purchase price. In no instance shall DWYER be liable for
incidental or consequential damages arising from a breach of warranty, or from the use or
installation of its products.
No representative or person is authorized to give any warranty other than as set out above or to
assume for DWYER any other liability in connection with the sale of its products.
SS2092 Rev A 11/11/02
Dwyer Instruments, Inc.
102 Indiana Highway 212
Michigan City, Indiana 46360, U.S.A.
Phone: 800-872-9141/219-879-8868
Fax: 219/872-9057
Lit-By Fax: 888/891-4963
www.dwyer-inst.com
e-mail: info@dwyer-inst.com
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1

OPERATING INSTRUCTIONSSeries 681SANITARY PRESSURE TRANSMITTERSGENERAL INFORMATIONYour Dwyer Series 681Sanitary Pressure Transmitter has been carefully

Seite 2 - RETURNING PRODUCTS FOR REPAIR

2 3Venting - The 681 is vented to atmosphere through the cable to achieve best accuracy.This is particularly important for models with pressure ranges

Kommentare zu diesen Handbüchern

Keine Kommentare